Home / Guides / Concrete Cube Testing Procedure (IS 516): Step-by-Step Guide
How to choose

Concrete Cube Testing Procedure (IS 516): Step-by-Step Guide

Written by the counter team at Multi Trade Combines — 35 years supplying NE workshops. Concrete cube testing is mandatory under IS 456 for all structural concrete in India. This guide covers the complete procedure — mould preparation to CTM reading — based on IS 516 and the practical experience of laboratories we have supplied across Northeast India.

Purpose and standards

Written by the counter team at Multi Trade Combines — 35 years supplying NE workshops.

Concrete cube testing is the primary quality-control check for structural concrete across India. IS 456 (Plain and Reinforced Concrete Code of Practice) mandates that concrete must be tested by casting cube specimens per IS 516 (Method of Tests for Strength of Concrete) at specified frequencies during construction. Multi Trade Combines supplies ISI-marked cast-iron cube moulds and Compression Testing Machines (CTM) to civil labs and construction site QC setups across Northeast India. Browse our full Civil Lab Equipment catalogue.

Equipment required

EquipmentSpecification / Source
Cube mould150 mm cast-iron ISI-marked (IS 10086) — Multi Trade Combines stock
Tamping rod16 mm dia., 600 mm long, rounded end — for manual compaction
Vibrating tableFor mechanically compacted specimens (IS 516 preferred method)
Curing tankWater tank at 27°C ± 2°C for minimum 28 days
Compression Testing Machine1000 kN capacity for M15–M40; 2000 kN for M50+ — Multi Trade Combines stock
Steel rule and marking penFor numbering and identifying specimens

Procedure — step by step

8 steps from fresh concrete sample to compressive strength value

  1. Prepare the mould. Clean the inside surfaces of the cast-iron cube mould thoroughly, removing any hardened concrete from previous use. Apply a light coat of oil (shuttering oil or machine oil) to all interior surfaces. Assemble the mould, check that all bolts are tight, and place it on a firm, level, non-vibrating surface.
  2. Sample the fresh concrete. Take the sample from the middle of the batch or transit mixer drum — not from the first or last discharge, which may be segregated. Collect at least 6 litres of concrete for a set of 3 cubes. Take the sample within 5 minutes of discharge; do not allow it to begin setting.
  3. Fill and compact the mould. Fill the mould in two layers, each approximately 75 mm deep. Compact each layer using 35 strokes of the tamping rod, distributed uniformly across the surface, or use a vibrating table (preferred): vibrate until air bubbles cease rising to the surface. Overfill slightly, then strike off the top surface level with the top of the mould using a steel trowel to produce a flat face.
  4. Mark and store for initial set. Mark the top surface with the specimen ID (date, mix identification, pour location) using a marking pen or pressed steel stamp. Cover the mould with a damp hessian cloth or polythene sheet to prevent moisture loss. Leave on a vibration-free surface at ambient temperature for 24 hours before demoulding. Do not disturb or move the cubes during this period.
  5. Demould and transfer to curing tank. After 24 hours (±30 minutes), carefully remove the mould fasteners and slide apart the mould walls without striking or jolting the specimen. Transfer the cube immediately to the curing water tank. The water temperature must be maintained at 27°C ± 2°C — in Northeast India's winter months (November–January), this often requires a tank heater, particularly in Meghalaya and Arunachal Pradesh hill stations where ambient temperature can drop below 15°C.
  6. Cure for the required test age. Standard test ages are 7 days (early indication only) and 28 days (structural acceptance). Keep cubes fully submerged throughout. Remove from water 24 hours before testing to allow surface moisture to evaporate.
  7. Test on the Compression Testing Machine. Place the cube in the CTM with one of the cast faces (side face, not top or bottom) in contact with the platens — the cast top surface is not perfectly flat. Apply load at a uniform rate of 140 kg/cm² per minute (14 N/mm²/min) as per IS 516. Record the maximum load at failure (peak load displayed on the CTM's digital indicator).
  8. Calculate compressive strength. Compressive strength (N/mm²) = Maximum load (N) ÷ Cross-sectional area (mm²). For a 150 mm cube: area = 150 × 150 = 22,500 mm². Example: failure load 675,000 N → strength = 675,000 ÷ 22,500 = 30 N/mm² = M30 equivalent. Report results for the average of three specimens from the same sample.

Acceptance criteria (IS 456)

For M25 concrete: no individual cube result should fall below fck − 3 N/mm² (22 N/mm²); the average of any group of 4 consecutive results must not be below fck (25 N/mm²). Similar acceptance rules apply to all grades — refer to IS 456 Clause 15.2 for the complete table. In NE India's monsoon construction season, the most common cause of borderline results is excess water in the mix from wet aggregate — test aggregate moisture content regularly from June to September.

Related products

Frequently Asked Questions

Why is the 28-day cube test the standard for structural acceptance?

Concrete gains strength progressively through cement hydration. At 7 days it reaches approximately 65–70% of its 28-day strength; at 28 days it reaches the specified characteristic compressive strength (fck). IS 456 specifies 28-day cube strength as the acceptance criterion because this is when the concrete structure begins taking its design loads in most construction sequences. 7-day results are used for early indication only — a 7-day strength below 65% of the specified value is a warning flag that warrants investigation without waiting for the 28-day result.

What if my cube results are failing for an ongoing pour in Assam?

First, check the sampling and testing procedure — most in-field failures are procedural: incorrect compaction, cubes moved before 24-hour initial set, or specimen damaged during transport to the lab. If procedure was correct, review the mix: water-cement ratio may have increased due to wet aggregate or excess water added on site. In Northeast India's monsoon, wet aggregate from stockpiles can add 3–5% extra water to the mix without the batching crew accounting for it — this is the most common cause of low-strength results. Core testing of in-situ concrete per IS 516 Part 4 is the next step if cube results remain consistently low.

What size cube moulds does Multi Trade Combines stock?

We stock 150 mm cast-iron ISI-marked cube moulds and 100 mm cube moulds for higher-strength concrete (M60 and above, where smaller specimens are used for machine range compatibility). Both comply with IS 10086. We also stock PVC cube moulds as a lightweight alternative for sites where transporting heavy cast-iron moulds is impractical — these are single-use or limited-reuse but significantly lighter than cast iron.